NEMA Non-Locking Receptacle Configurations and Grounding
Identify 37 non-locking NEMA receptacle configurations, separating voltage, current, current-carrying poles, neutral and protective earth.
Quick answer
R denotes a receptacle and P a plug; the archived R faces are not same-view plug pin diagrams. Series 5 is 125 V grounding and series 6 is 250 V grounding. Legacy series 10 lacks a separate protective earth: neutral W is not G.
Scope
The ten classification rows and 37 receptacle forms are retained. A notation such as 2/3 counts current-carrying poles/total wires, excluding protective earth from the pole count. Original drawings show receptacle face features, not dimensions, rear terminals or rewiring instructions.
Reading example
A 5-20R is a 125 V, 20 A, two-pole three-wire grounding receptacle. A 6-20R is 250 V and has different slots. The shared “20” does not establish voltage or adapter compatibility.
Legacy tables with visible corrections
Legacy source notes and applicability
These notes retain the legacy record. For corrected facts and applicability, use this page’s quick answer, scope and visible table corrections.
2-20R
2-30R
5-15R
5-20R
5-30R
5-50R
6-15R
6-20R
6-30R
6-50R
7-15R
7-20R
7-30R
7-50R
10-20R
10-30R
10-50R
11-15R
11-20R
11-30R
11-50R
14-15R
14-20R
14-30R
14-50R
14-60R
15-15R
15-20R
15-30R
15-50R
15-60R
18-15R
18-20R
18-30R
18-50R
18-60R
Green: Ground
Blue: Neutral
Black: Hot/Line
Frequently asked questions
Does physical fit establish suitability?
No. Confirm the specified configuration, equipment voltage/frequency, current, earthing and local requirements. Do not reshape pins or remove protective earth.
Can the receptacle face be copied directly to a plug face?
No. Mating faces may be mirrored, and rear terminals are different views. Use the actual G/W/X/Y/Z markings and manufacturer drawing.