10kV / 0.4kV Transformer — Primary/Secondary Rated Current
        Field
            Capacity S (kVA)
            Primary I₁e (A)
            Secondary I₂e (A)
        Input:
            
            —
            —
        Voltage
            
            Note: Enter S only and/or change voltages. Quick factors: 40.5kV I₁e≈0.017S; 12kV I₁e≈0.06S; 7.2kV I₁e≈0.10S; when secondary is 0.4kV, I₂e≈1.443S.
        
    Three-Phase Motor (0.4kV) Rated Current
        Field
            Power P (kW)
            Rated Current (A)
            Factor
        Input:
            
            —
            I≈0.76P / 0.4kV ⇒ I≈1.9P
        
            Considering η and cosφ combined, take Ie≈0.76·P / U(kV). For 0.4kV: I≈1.9·P (A).
        
    Single-Phase Motor (220V) Rated Current
        Field
            Power P (kW)
            Rated Current (A)
            Factor
        Input:
            
            —
            Quick rule: I≈5.7P (A)
        
            Note: Results are quick estimates; refer to datasheets for exact values. η and cosφ will affect current.